Strany 1 - SPEEDMASTER

SPEEDMASTER®SM2 Series Flux VectorSM4 Series Flux VectorInstallation and Operation ManualA Regal Brand

Strany 2 - Contents

9Installation Drives must not be installed where subjected to adverse environmental conditions such as: combustible, oily, or hazardous vapors or dust

Strany 3 - About these instructions

10Installation Drives must not be installed where subjected to adverse environmental conditions such as: combustible, oily, or hazardous vapors or dus

Strany 4 - Safety information

11Installation174603 174604 1746051746511746521746531746543.2.1 Power ConnectionsDANGER!Hazard of electrical shock! Circuit potentials are up to 600

Strany 5 - 1 Safety information

12InstallationAll three-phase models(3/PE AC)3.2.1.3 Mains connection to Three-Phase SupplyPE L1 L2 L3PE L1 L2 L33.2.1.4 Motor Connection U/T1

Strany 6 - Technical data

13Installation3.2.1.6 NEMA 4X (IP65) Input Terminal BlockFor NEMA 4X (IP65) models with integrated EMC filter and/or integrated line disconnect, the i

Strany 7

14Installation3.2.1.7 Dynamic Brake ConnectionsFor NEMA 1 and NEMA 4X Drives rated up to 25 HP the Dynamic Brake connections are made as illustrated

Strany 8

15Installation3.2.2 Fuses/cable cross-sectionsNoteObserve local regulations. Local codes may supersede these recommendationsTypeRecommendationsFuseM

Strany 9 - 3 Installation

16InstallationObserve the following when using Ground Fault Circuit Interrupters (GFCIs):• Installation of GFCI only between supplying mains and contr

Strany 10 - Installation

17CommissioningControl Terminal Strip for 15HP (11 kW) and Greater Drives:62541113A13B13CTXA51214 302AOUTDIGOUT2k … 10k+10 V+12 VAINAINCOMCOMALsw1716T

Strany 11

18CommissioningDisplay START BUTTONRUNIn Local Mode (P100 = 0, 4, 6), this button will start the drive.STOP BUTTONSTOPStops the drive, regardless of w

Strany 12

11 Safety information ...32 Technical data ...

Strany 13

19CommissioningNOTEIf the keypad is selected as the auto reference (P121…P124 is 6) and the corresponding TB-13 input is closed, the AUTO LED and s t

Strany 14

20CommissioningDisplay START CONTROLThe REMOTE/LOCAL LEDs indicate the current start control source. If the start control source is a remote keypad or

Strany 15

21Commissioning4.3 Parameter settingStatus/fault messages Change ParametersStoP60.0F.AFF.UFCLErrp100p104p54160 sP194 = 0000PASS0225MM15 sMM20.012.0V

Strany 16

22Commissioning4.5 Parameter menu4.5.1 Basic Setup ParametersCode Possible SettingsIMPORTANTNo. Name Default SelectionP100Start Control Source0 0 L

Strany 17

23CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP101Standard Reference Source0 0 Keypad (Local or Remote) Selects the default

Strany 18 - 4 Commissioning

24CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP108Motor Overload 100 30 {%} 100P109Motor Overload Type0 0 Speed Compensati

Strany 19

25CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionNote• P110 = 0, 2: Start command must be applied at least 2 seconds after po

Strany 20

26Commissioning4.5.2 I/O Setup ParametersCode Possible SettingsIMPORTANTNo. Name Default SelectionP113Auto/Manual Control00 Terminal Strip ControlTh

Strany 21

27CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP121P122P123p124TB-13A Input FunctionTB-13B Input FunctionTB-13C Input Functio

Strany 22

28CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionWARNING!If the input dened to “Start Sequence” is opened during a sequence, t

Strany 23

This documentation applies to the SM2 and SM4 Vector frequency inverter, and contains important technical data and describes installation, operation,

Strany 24

29CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP131Preset Speed #1 0.0 0.0 {Hz} 500PRESET SPEED13A 13B 13C 13D1 X -- -- --2

Strany 25

30CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP140(cont)Relay Output TB-16, 170 11 Local Keypad Control ActiveEnergizes when

Strany 26

31CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP144Digital Output InversionUsed to invert the selections for P140 (Relay Outp

Strany 27

32CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP154TB-30 Scaling: Torque100 10 {%} 1000 If P150 = 5 or 6, sets the Torque (a

Strany 28

33Commissioning4.5.3 Advanced Setup ParametersCode Possible SettingsIMPORTANTNo. Name Default SelectionP160Speed at Minimum Signal0.0 -999.0 {Hz} 1

Strany 29

34CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP167(1)Base Frequency 60.0 10.0 {Hz} 1500 V0112P168Fixed Boost 0.0 {%} 30.0

Strany 30

35CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP175DC Brake Time 0.0 0.0 {s} 999.9NoteCONFIRM MOTOR SUITABILITY FOR USE WITH

Strany 31

36CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP181Skip frequency 1 0.0 0.0 {Hz} 500 • Drive will not run in the dened ski

Strany 32

37CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP197Clear Fault History0 0 No Action1 Clear Fault HistoryP199Program Selecti

Strany 33

38Commissioning4.5.4 PID ParametersCode Possible SettingsIMPORTANTNo. Name Default SelectionP200PID Mode 0 0 Disabled • Normal-acting: As feedback

Strany 34

All safety information given in these Operating Instructions have the same layout:Signal Word! (characterizes the severity of the danger)Note (describ

Strany 35

39CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP207Proportional Gain5.0 0.0 {%} 100.0 Used to tune the PID loop:• Increase

Strany 36

40CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP244Sleep Entry Mode0 0 Enter SLEEP if Drive Speed <P240For time lon

Strany 37

41Commissioning4.5.5 Vector ParametersCode Possible SettingsIMPORTANTNo. Name Default SelectionP300(1)Drive Mode 0 0 Constant V/Hz Constant torque V

Strany 38

42CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP310(1)Motor Stator Resistance0.00 0.00 {Ω} 64.00 • Will be automatically pro

Strany 39

43CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP399Motor Auto-calibration0 0 Calibration Not Done • If P300 = 4 or 5, motor

Strany 40

44Commissioning4.5.6 Network ParametersCode Possible SettingsIMPORTANTNo. Name Default SelectionP400Network Protocol0 Not Active This parameter will

Strany 41

45CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP405Current Network Fault0 No Fault1 F.nF1 Netldle Mode2 F.nF2 Loss of E

Strany 42

46CommissioningCodeDisplay Range (READ ONLY)IMPORTANTNo. NameP512Heatsink Temp 0 {°C} 150 Heatsink temperatureP5200-10 VDC Input 0.0 {VDC} 10.0 Act

Strany 43

47CommissioningCodeDisplay Range (READ ONLY)IMPORTANTNo. NameP562Sequencer: TimeRemaining in Active Segment0.0 {P708} 6553.50

Strany 44

48Commissioning4.5.8 Onboard Communications Parameters 15-30HP (11-22kW)The P6xx Onboard Communication parameters are applicable to the 15HP (11kW) a

Strany 45

1 Safety informationGeneral DANGER! Some parts of LEESON controllers can be electrically live and some surfaces can be hot.Non-authorized r

Strany 46

49CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP626Network Timeout Action4 0 No action Modbus1 Stop (P111)2 Quick Stop3 C

Strany 47

50CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP706Sequencer: Action after Stop/Start transition or Fault Restart00 Restart

Strany 48

51CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP718Segment #2Digital Output State0Bit0 Relay bit = 0: OFF (De-energized)bit =

Strany 49

52CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionSegment #5P730Segment #5 Frequency Setpoint0.0-500.0 {Hz} 500.0 If P112 = 1,

Strany 50

53CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP743Segment #7Digital Output State0Bit0 Relay bit = 0: OFF (De-energized)bit =

Strany 51

54CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionSegment #10P755Segment #10 Frequency Setpoint0.0-500.0 {Hz} 500.0 If P112 =

Strany 52

55CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP768Segment #12Digital Output State0Bit0 Relay bit = 0: OFF (De-energized)bit

Strany 53

56CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionSegment #15P780Segment #15 Frequency Setpoint0.0-500.0 {Hz} 500.0 If P112 =

Strany 54

57CommissioningCode Possible SettingsIMPORTANTNo. Name Default SelectionP793End Segment:Digital Output StateBit0 Relay bit = 0: OFF (De-energized)bit

Strany 55

58Commissioning4.5.9.1 Sequencer ParametersWARNINGIf the input dened to “Start Sequence” is opened during a sequence, the drive will exit sequencer

Strany 56

5Technical data2 Technical data2.1 Standards and application conditionsConformityCE Low Voltage Directive (73/23/EEC)ApprovalsUL 508C Underwriters

Strany 57

59Commissioning4.5.9.2 Sequencer Parameters 2P715P716P717 1P710P711P7124P725P726P7273P720P721P7226P735P736P7375P730P731P732 8P745P746P747 7P740P741P7

Strany 58

60Commissioning4.5.9.3 Sequencer StatusNOTEOn the “End Segment”, the output voltage is not present until after the end segment delay P792 has expired

Strany 59

61Troubleshooting and Diagnostics5 Troubleshooting and Diagnostics5.1 Status/Warning MessagesStatus / Warning Cause RemedybrDC-injection brake acti

Strany 60

62Troubleshooting and DiagnosticsStatus / Warning Cause RemedyPdeCPID Deceleration Status PID setpoint has nished its ramp but the drive is still dec

Strany 61

63Troubleshooting and Diagnostics5.2 Drive Conguration MessagesWhen the Mode button is pressed and held, the drive’s display will provide a 4-digit

Strany 62 - 5.1 Status/Warning Messages

64Troubleshooting and Diagnostics645.3 Fault MessagesThe messages below show how they will appear on the display when the drive trips. When looking

Strany 63

65Troubleshooting and DiagnosticsFault CauseRemedy (1)f.HFHigh DC Bus Voltage faultMains voltage is too high Check mains voltage and P107Decel time is

Strany 64

66Troubleshooting and Diagnostics66Fault CauseRemedy (1)f.OF1Output fault: Ground faultGrounded motor phase Check motor and motor cableExcessive capa

Strany 65 - 5.3 Fault Messages

Appendix AA.1 Permissable Cable LengthsThe table herein lists the permissable cable lengths for use with an SM Flux Vector inverter with an internal

Strany 66

Important InformationResale of Goods In the event of the resale of any of the goods, in whatever form, Resellers/Buyers will include the following lan

Strany 67

6Technical data2.2 Ratings120VAC Doubler / 240VAC ModelsTypePower[Hp/kW]Mains Output CurrentSM2 WattsLossSM4 Watt LossVoltage(1)Iin (120V) Iin (240V

Strany 68 - Appendix

©2013 Regal-Beloit Corporation SM2-SM4 Rev 07-13 7581S/7-13/BH Printed in the USAA Regal BrandLEESON ElectricGrafton, Wisconsin 53024 U.S

Strany 69 - Important Information

7Technical data480VAC ModelsTypePower[Hp/kW]Mains Output CurrentSM2 WattsLossSM4 Watts LossVoltage(1)IinInCLimmax(2)400V 480V 400V 480V 400V 480V1746

Strany 70 - A Regal Brand

Drives must not be installed where subjected to adverse environmental conditions such as: combustible, oily, or hazardous vapors or dust; excessive m