Installation and Operation ManualSPEEDMASTER®SM SERIES SUB-MICRO INVERTERS

Strany 2

65.0 SM Series™RATINGSSM INPUT OUTPUTMODEL FOR MOTORS 50-60 Hz) (3 Phase) HEAT LOSSNUMBER RATED INPUT CURRENT POWER CURRENT (WATTS)(NOTE 1) HP kW PHAS

Strany 3 - LEESON Electric

6.0 INSTALLATIONNOTE: SM Series™drives are intended for inclusion within other equipment, by professional electrical installers according to EN 61000-

Strany 4 - IMPORTANT NOTICE

87.0 INPUT AC POWER REQUIREMENTSHazard of electrical shock! Capacitors retain charge after power is removed.Disconnect incoming power and wait until t

Strany 5 - 1.0 GENERAL

97.2 INPUT FUSING AND DISCONNECT REQUIREMENTSA circuit breaker or a disconnect switch with fuses must be provided in accordance with the NationalElect

Strany 6

107.3 INSTALLATION ACCORDING TO EMC REQUIREMENTSThe SM Series™Series can be installed to meet the European stan-dards Electromagnetic Compatibility (E

Strany 7 - 1.6 CUSTOMER MODIFICATION

8.1 INPUT AND OUTPUT WIRINGOn single phase input models, wire the input power to terminals L1 and L2/N. On three phase inputmodels, wire the input pow

Strany 8 - DIMENSIONS

12Do not connect incoming AC power to output terminals U, V, or W, or terminals B+, B-!. Severe damage to the drive will result.NOTES:1. WIRE AND GROU

Strany 9 - SPECIFICATIONS

10.0 CONTROL WIRING10.1 CONTROL WIRING VS. POWER WIRINGExternal control wiring MUST be run in a separate conduit away from all other input and output

Strany 10 - 5.0 SM Series

1410.6 SPEED REFERENCE SELECTIONIf an analog speed reference input is used to control the drive speed, terminal TB-13A, 13B, or 13E(Parameter 10, 11,

Strany 11 - 6.0 INSTALLATION

15NOTE: If TB-13A, TB-13B, and TB-13E are all programmed to select speed references, and twoor three of the terminals are closed to TB-11, the higher

Strany 12

TABLE OF CONTENTS1.0 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12.0 SM Series™DIMENSIONS . . .

Strany 13 - INPUT WIRE SIZE REQUIREMENTS

1611.0 SM Series™CONTROL WIRING DIAGRAMS11.1 SM Series™TERMINAL STRIPShown below is the control terminal strip, along with a brief description of the

Strany 14 - 8.0 POWER WIRING

11.2 TWO-WIRE START/STOP CONTROLNOTES:1. Close TB-1 to TB-11 to RUN and open to STOP. TB-1 functions as a RUN input for two-wire start/stop circuits,

Strany 15

1811.3 THREE-WIRE START/STOP CONTROLNOTES:1. Program TB-13E (Parameter 12) for START FORWARD (06).2. If reverse direction is required, set ROTATION (P

Strany 16 - POWER WIRING DIAGRAM

1911.4 PRESET SPEEDS AND SPEED POT (WITH TWO-WIRE START/STOP CONTROL)NOTES:1. For preset speed control, all or some of the TB-13 terminals must be pro

Strany 17 - 10.0 CONTROL WIRING

2012.0 INITIAL POWER UP AND MOTOR ROTATIONDO NOT connect incoming AC power to output terminals U, V, and W or terminals B+, B-! Severe damage to the d

Strany 18

21Follow the procedure below to check the motor rotation. This procedure assumes that the drive has beenpowered up for the first time, and that none o

Strany 19 - SM SERIES™

2213.0 PROGRAMMING THE SM Series™DRIVEThe drive may be programmed by one of two methods: using the three buttons and 3-digit LED displayon the front o

Strany 20 - CONTROL WIRING DIAGRAMS

Use the L and M buttons to scroll to the desired parameter number. In the example below, Parameter19 is being displayed, which is the ACCELERATION TIM

Strany 21 - 1 2 5 6 11 13A 13B 13E 25

13.1 SETTING VALUES IN TENTHS OF UNITS ABOVE 100Parameter settings and the keypad speed command can always be adjusted in tenths of unit incrementsfro

Strany 22

2513.2 ELECTRONIC PROGRAMMING MODULE (EPM)Every SM Series™drive has an Electronic Programming Module (EPM) installed on the main controlboard. The EPM

Strany 23

INPUT POWERTERMINALSELECTRONICPROGRAMMINGMODULE (EPM)PROGRAMMINGBUTTONSOUTPUT (MOTOR) TERMINALS3-DIGIT LEDDISPLAYCONTROLTERMINALSTRIPDC BUS TERMINALSS

Strany 24

2614.0 PARAMETER MENUFACTORYNO. PARAMETER NAME RANGE OF ADJUSTMENTDEFAULT01 LINE VOLTAGE HIGH (01), LOW (02) HIGH (01)02 CARRIER FREQUENCY 4kHz (01),

Strany 25

FACTORYNO. PARAMETER NAME RANGE OF ADJUSTMENTDEFAULT12 TB-13E FUNCTION NONE (01), 0-10 VDC (02), 4-20mA (03), NONE (01)SELECT PRESET SPEED #3 (04), IN

Strany 26

28FACTORYNO. PARAMETER NAME RANGE OF ADJUSTMENTDEFAULT30 SLIP COMPENSATION 0.0 - 5.0 % 0.0 %31-37 PRESET SPEEDS 0.0 - MAXIMUM FREQUENCY 0.0 Hz38 SKIP

Strany 27

2915.0 DESCRIPTION OF PARAMETERSP01 LINE VOLTAGE SELECTIONThis calibrates the drive for the actual applied input voltage. Set this parameter to HIGH (

Strany 28

3003 START WITH DC BRAKE: When a START command is given, the drive will apply DCBRAKE VOLTAGE (Parameter 22) for the duration of DC BRAKE TIME (Parame

Strany 29

3104 RAMP WITH DC BRAKE: When a stop command is given, the drive will decelerate the motor down to 0.2 Hz (at the rate set by Parameter 20 - DECELERAT

Strany 30 - 14.0 PARAMETER MENU

3209 AUTOMATIC SPEED MODE: Closes if an AUTOMATIC (terminal strip) speed reference isactive. Opens if a STANDARD (Parameter 5) speed reference is acti

Strany 31

33P11 TB-13B FUNCTION SELECTThis selects the function of terminal TB-13B. Closing TB-13B to TB-11 (or opening in the case of setting 09 and 11) activa

Strany 32

13 REMOTE KEYPAD: When the Remote Keypad option is being used, TB-13B must be set tothis function. Also, TB-13E (Parameter 12) must be set for REMOTE

Strany 33

The following output functions can be selected. The terms “open” and “close” refer to the state of theinternal transistor that activates the circuit.

Strany 34

IMPORTANT NOTICEThe following , and information is supplied to you for yourprotection and to provide you with m

Strany 35

36P16 UNITS EDITINGThis allows parameter and keypad speed editing in whole units or tenths of units above 100. Below 100,the value can always be chang

Strany 36

37P22 DC BRAKE VOLTAGEThis sets the magnitude of the DC braking voltage, in percentage of the line voltage. The point at whichthe DC braking is activa

Strany 37

38P26 MOTOR OVERLOADThe SCL/SCM Series is UL approved for solid state motor overload protection, and therefore does not require a separate thermal ove

Strany 38

39P30 SLIP COMPENSATIONSLIP COMPENSATION is used to counteract changes in motor speed (slip) caused by changes in load.In a standard AC induction moto

Strany 39

40Example: The critical frequency is 23 Hz, and it is desired to skip a frequency range of 3 Hz above andbelow the critical frequency (therefore the s

Strany 40

41P44 PASSWORDThis allows the PASSWORD to be changed to any number between 000 and 999. Setting PASSWORDto 000 disables the password function.NOTE: Th

Strany 41

4203 RESET OEM: Resets the user parameters to the OEM default settings. If the drive is not programmed with OEM default settings, the display will fla

Strany 42

43P51 SOFTWARE VERSIONThis displays the software version number for the control board software. This information is useful whencontacting the factory

Strany 43

44P57 TERMINAL STRIP STATUSThis indicates that status of several terminals using the vertical segments of the LED display. An illuminated segment indi

Strany 44

16.0 TROUBLESHOOTINGTo aid in troubleshooting, Parameters 50 through 60 can be accessed without entering the PASSWORD.Simply press the Mode button twi

Strany 45

1.0 GENERAL1.1 PRODUCTS COVERED IN THIS MANUALThis manual covers the LEESON Electric SM Series™Variable Frequency Drive.1.2 PRODUCT CHANGESLEESON Elec

Strany 46

46The table below lists the fault conditions that will cause the drive to shut down, as well as some possiblecauses. Please contact the factory for mo

Strany 47

17.0 SM Series™DISPLAY MESSAGESThe following describes the various displays and messages that can appear on the SM Series™drive.17.1 SPEED DISPLAYIf t

Strany 48

48NOTE: The speed source displays will flash when the speed reference source is changed while thedrive is running to indicate that the new speed refer

Strany 49 - 16.0 TROUBLESHOOTING

EC DECLARATION OF CONFORMITYIn accordance with EN45014:1998Applied Council Directive(s): EMC Directive 89/336/EEC, as amended: 92/31/EECand 93/63/EEC,

Strany 50

REV3/5184S/5K/10-05/CP/SK-BHService Dept. FAX (262)-377-0090A REGAL-BELOIT COMPANYA REGAL-BELOIT COMPANY

Strany 51 - DISPLAY MESSAGES

1.5 SAFETY INFORMATIONGeneralAll operations concerning installation and commissioning, as well as maintenance, must be carried outby qualified, skille

Strany 52

1.6 CUSTOMER MODIFICATIONLEESON Electric welcome the opportunity to assist our customers in applying our products. Many customizing options are availa

Strany 53

4HP INPUT INPUT SM(kW) VOLTAGE PHASE MODEL H W D P R0.33 120 1 174263 5.75 (146) 2.88 (74) 3.26 (83) 0.28 (7) 4.37 (111)(0.25) 208/240 1 174267 5.75 (

Strany 54 - REV3/5184S/5K/10-05/CP/SK-BH

54.0 SM Series™SPECIFICATIONSStorage Temperature -20° to 70° CAmbient Operating Temperature 0° to 40° C (derate 2.5% per °C above 40°)Ambient Humidity