Leeson SM Series Sub-Micro Inverters Uživatelský manuál Strana 20

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 54
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 19
16
11.0 SM Series
CONTROL WIRING DIAGRAMS
11.1 SM Series
TERMINAL STRIP
Shown below is the control terminal strip, along with a brief description of the function of each terminal.
The following wiring diagram examples provide a quick reference to wire the drive for the most common
configurations.
NOTE: The function of terminals TB-13A, TB-13B, TB-13E and the Form A relay at terminals
16 and 17 are dependent on the programming of certain parameters. Refer to Section 15.0 -
DESCRIPTION OF PARAMETERS.
The digital inputs (terminals 1, 13A, 13B, and 13E) are active-high. They can be activated using
terminal 11 (which is +12 VDC) as shown in the following diagrams, or by using an external
voltage source with a range of +12 VDC to +28 VDC (± 10%).
1 2 5 6 11 13A 13B 13E 25
16 17
MAINTAINED
RUN/STOP
CONTACT
FORM A
RELAY
RUN
SIGNAL COMMON
0-10 VDC INPUT
SPEED POT POWER SUPPLY
DIGITAL INPUT REFERENCE
TB-13A FUNCTION SELECT
TB-13B FUNCTION SELECT
TB-13E FUNCTION SELECT
4-20 mA INPUT
Zobrazit stránku 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 53 54

Komentáře k této Příručce

Žádné komentáře